Detail AEMC Ground Resistance Tester Model 6471

Alat Laboratorium Mikrobiologi

Deskripsi produk
Ground Resistance Tester Model 6471
The Digital Ground Resistance Tester Model 6471 is a portable measurement instrument designed to measure Ground Resistance with 2 clamps (sold separately), no auxiliary rods, Bond/Connection Resistance (2-Pole and 4-Pole Kelvin sensing), Ground Resistance (3-Pole or 4-Pole), Ground Coupling Resistance, and Selective Ground Resistance, Soil Resistivity (Wenner or Schlumberger method). The Model 6471 measures from 0.01 to 99.99kΩ and is auto-ranging, automatically seeking out the optimum measurement range, test frequency and test current.

Specifications :

4-Point Earth Resistance Measurement
Range (Auto-Ranging)
0.01Ω to 99.99kΩ
Resolution
0.001 to 10Ω
Accuracy
±(2% Reading +1ct)
Test Voltage
16 or 32V; 41 to 513Hz
Test Current
Up to 250mA
Selective 4-Pole (with optional probes MN82 or SR182)
Same characteristics as with 4-point earth resistance measurement
3-Point Earth Resistance Measurement
Range (Auto-Ranging)
0.09Ω to 99.9kΩ
Resolution
0.01 to 100Ω
Accuracy
±(2% Reading +1ct)
Test Voltage
16 or 32V; 41 to 513Hz
Test Current
Up to 250mA
Soil Resistivity 4-Point Measurement
Test method
Wenner or Schlumberger selectable with automatic calculation
Range (Auto-Ranging)
0.01Ω to 99.9kΩ; ρ max: 999kΩm
Resolution
0.01 to 100Ω
Accuracy (Typical)
±(2% Reading +1ct)
Test Voltage
16 or 32V; 41 to 128Hz selectable
2 Clamp Ground Measurement (with optional probes MN82 or SR182)
Range (Auto-Ranging)
0.1 to 500Ω
Resolution
0.01 to 1Ω
Measurement Frequency
Auto: 1611Hz; Manual: 128Hz-1367Hz-1611Hz-1758Hz
DC Resistance Measurement (Bond Testing)
2-Pole (with lead resistance compensation) or 4-Pole (Kelvin sensing)
Range (Auto-Ranging)
2-pole: 0.12Ω to 99.9kΩ
4-pole: 0.020Ω to 99.99kΩ
Resolution
2 -pole: 0.01 to 100Ω
4-pole: 0.001 to 10Ω
Accuracy (Typical)
±(2% Reading +2ct)
Test Voltage
16V DC; (+, - or auto polarity)
Test Current
Up to 250mA
Current Measurement (with optional probes MN82 or SR182)
Range
0.01mA to 40A, 16 to 400Hz
Accuracy (Typical)
±(3% Reading +2ct) typical
External Voltage Measurement
Range
0.1 to 65V AC/DC – DC, 15 to 440Hz
Accuracy
±(2% Reading +1ct)
General Features
Memory
512 measurements (64KB)
Communication
USB 2.0 optically isolated, DataView software included
Power Source
9.6V rechargeable battery pack with external 110/220V charger
Battery Life
1500 tests typical in automatic mode
Dimensions
10.7 x 9.80 x 5.12” (272 x 248 x 130mm)
Weight
7lbs (3.2kg) with battery
Case
UL V0 Polypropylene
Operating Temperature
32° to +113°F (0° to +45°C)
Storage Temperature
-40° to 158°F (-40° to +70°C)
Relative Humidity
Up to 90%
Ingress Protection (IP)
IP 53 with cover closed
EMC
EN 61326-1
Safety Compliance
IEC 61010-1, EN 61557, 50V CAT IV, Pollution Degree 2





VT/PT Ratio Range
Auto-Ranging: 0.8000:1 to 8000.0:1

VT/PT Accuracy
0.8000 to 9.9999: ±0.2% of Reading

10.000 to 999.99: ±0.1% of Reading

1000.0 to 4999.9: ±0.2% of Reading

5000.0 to 8000.0: ±0.25% of Reading

CT Ratio Range
Auto-Ranging: 0.8000 to 1000.0

CT Accuracy
±0.5% of Reading

Excitation Signal
VT/PT Mode: 32Vrms max

CT Mode: Auto Level 0 to 1A, 0.1 to 4.5Vrms

Excitation Current Display
Range: 0 to 1000mA

Accuracy: ±(2% of Reading +2mA)

Excitation Frequency
70Hz

Display
LCD 16 character, 2 line, large format, LED backlight, day/night visible

Languages Supported
English, Spanish, French, Italian, German, Portuguese

Communication
Optically isolated USB 2.0

Data Storage
Up to 10,000 complete measurements

Power Source
Two rechargeable 12V NiMH batteries (included)

Battery Life
Up to 10 hours of continuous operation

Low Battery Indication
LED and LCD

External Charger
90 to 240V, 50/60Hz (smart charger)

Charging Time
<4 hours

Measurement Method
In accordance with ANSI/IEEE Std. C57.12.90-2006

Software
DataView analysis software included

Dimensions
10.70 x 9.76 x 5.12” (272 x 248 x 130mm)

Weight
8.1 lbs (3.7kg)

Operation Temperature
14° to 122°F (-10° to 50°C)

Storage Temperature
-4° to 140°F (-20° to 60°C)

Index of Protection
IP40 (lid open), IP53 (lid closed)

Double Insulated
Yes

CE Approved
Yes

Safety Compliance


IEC 61010-1 (1995-A2) 50V CAT IV Pollution 2

VT/PT Ratio Range
Auto-Ranging: 0.8000:1 to 8000.0:1

VT/PT Accuracy
0.8000 to 9.9999: ±0.2% of Reading

10.000 to 999.99: ±0.1% of Reading

1000.0 to 4999.9: ±0.2% of Reading

5000.0 to 8000.0: ±0.25% of Reading



CT Ratio Range
Auto-Ranging: 0.8000 to 1000.0

CT Accuracy
±0.5% of Reading

Excitation Signal
VT/PT Mode: 32Vrms max

CT Mode: Auto Level 0 to 1A, 0.1 to 4.5Vrms

Excitation Current Display
Range: 0 to 1000mA

Accuracy: ±(2% of Reading +2mA)

Excitation Frequency
70Hz

Display
LCD 16 character, 2 line, large format, LED backlight, day/night visible

Languages Supported
English, Spanish, French, Italian, German, Portuguese

Communication
Optically isolated USB 2.0

Data Storage
Up to 10,000 complete measurements

Power Source
Two rechargeable 12V NiMH batteries (included)

Battery Life
Up to 10 hours of continuous operation