Detail Earth Tester / Earth Resistance Meter PCE-ET 3000
Earth Tester / Earth Resistance Meter PCE-ET 3000
Instrument Laboratorium
Deskripsi produk
DESCRIPTION
Earth Tester / Earth Resistance Meter (resistance / voltage)
for houses and buildings
This earth tester / earth resistance meter is used to measure lightning-arresters or ground connection lightning-arresters for all kind of buildings. earth tester possesses a hermetic case and fulfils all the VDE 0413 safety requirements for the technical service operators. The earth tester is appropriate for measuring ground electrodes, lightning-arresters or little earth resistance systems as well as for measuring power resistance, conductive elements and coupling components.
Modern switching circuits reduce the influences of both pressure and earth resistance of the surrounding earth electrodes. Calibration of the earth tester with the adjoining control mechanism avoids the loss of precision at measuring.
Frequency control of 850 Hz avoids the influence of scattered currents of the net and its harmonic elements. Besides, this tester has a filter incorporated to delete distorted signs. The earth tester is delivered with the factory calibration however it can also have ISO calibration certificate.
HIGHLIGHTS
Characteristics:
- 3 ½ positions LCD display (máx. 1999)
- High accuracy
- Battery indicator / of range superation
- Data Hold
- Safety: IEC-1010-1 y CAT III 300 V
- Very good quality
- Components: checking cables: 15 m of red
cable, 10 m of yellow cable, 5 m of green
cable, ground needles, batteries and user
manual.
- Optional ISO calibration certificate.
Measuring earth resistance.
The earth tester is connected with the special ground components introduced on the earth by means of the checking cables. To make accurate measurements with this tester, ground has to be wet, if not ground will be wet. Ground components will be put in a straight line (place the black cable, then the green cable, the yellow one for one ground rod and finally the red cable for the second ground rod). Now everything is ready to connect the earth tester to check the earth connection of your building. This can be also used inside a building to check that water connections with earth work properly. This tester has been developed according to IEC 1010-1 standard and fulfils all the safety conditions for control electronic mechanism (CAT III).
SPECIFICATION
Technical specifications
Functions
Range
Resolution
Accuracy
Earth resistance
0 ... 19.99/ 0 ... 199/
y 0 ... 1999 Ω
10/ 100 mΩ / 1 Ω
± 2% + 2 positions
AC Stress
0 ... 200 V AC
50/60 Hz
0,1 V
± 3% + 2 positions
Lower measurement limit.
0.01 Ω
Current of measurement
2 mAeff / rms
Response time
aprox. 2.5 s
Measuring quota
4 s
Frequency
820 Hz
Overload range
in case of overlaoad, „1“ is shown
Power
6 x 1.5 V batteries
Dimensions
160 x 120 x 65 mm
Weight
560 g
Safety
IEC- 1010- 1; EN 61010- 1
instalation category: III
EMV
EN 50081- 1; EN 50082- 1
corresp. DIN/ VDE 0413 part 7
DELIVERY SCOPE
1 x Earth Tester / Earth Resistance Meter PCE-ET 3000
1 x Test cable set (15 m red, 10 m yellow, 5 m green)
1 x Set of earth rods
1 x User manual
Tampilkan Lebih Banyak