Detail Hioki AC/DC Clamp Meter CM4371
Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)
DC Current
20.00 A/600.0 A, Basic accuracy: ±1.3% rdg. ±0.08 A (20 A range)
AC Current
20.00 A/600.0 A (10 Hz to 1 kHz, True RMS), Basic accuracy: ±1.3% rdg. ±0.08 A (at 20 A)
Crest factor
20.00 A range: 7.5
600.0 A range: 3 or less
DC+AC Current
20.00 A/600.0 A (10 Hz to 1 kHz, True RMS), Basic accuracy:±1.3% rdg. ±0.13 A (at 20 A)
DC Voltage
600.0 mV to 1500 V, 5 ranges, Basic accuracy: ±0.5% rdg. ±3 dgt.
AC Voltage
6.000 V to 1000 V, 4 ranges (15 Hz to 1 kHz, True RMS), Basic accuracy: ±0.9% rdg. ±3 dgt.
DC+AC Voltage
6.000 V to 1000 V, 4 ranges, Basic accuracy: ±1.0% rdg. ±7 dgt.
Resistance
600.0 Ω to 600.0 kΩ, 4 ranges, Basic accuracy: ±0.7% rdg. ±5 dgt.
Electrostatic capacity
1.000 μF to 1000 μF, 4 ranges, Basic accuracy: ±1.9% rdg. ±5 dgt.
Frequency
9.999 Hz to 999.9 Hz, Basic accuracy: ±0.1% rdg. ±1 dgt.
Temperature (K)
-40.0 to 400.0 ˚C, add temperature probe accuracy to basic accuracy of ±0.5% rdg. ±3.0 ˚C
Voltage detection
Hi: 40 V to 600 V AC, Lo: 80 V to 600 V AC, 50/60 Hz
Other functions
Automatic AC/DC detection, Plus/Minus judgement function of DC A, DC V, Max/Min/Average/PEAK MAX/ PEAK MIN value display, Filter function, Display value hold, Auto hold, Back light, Auto-power save, Buzzer sounds, Zero-adjustment
Dustproof, waterproof
Grip: IP54 (when measuring an insulated conductor only), Jaw (the current sensor portion of the instrument)/ barrier: IP50 *Risk of electric shock from the conductor being measured increases when wet.
Power supply
LR03 Alkaline battery ×2, Continuous use 45 hr (Backlight OFF)
Core jaw diameter
69 mm (2.72 in) W× 14 mm (0.55 in) D, φ33 mm (1.30 in)
Dimensions and mass
65 mm (2.56 in) W × 215 mm (8.46 in) H × 35 mm (1.38 in) D mm, 340 g (12.0 oz)
Accessories
TEST LEAD L9207-10, CARRYING CASE C0203, LR03 Alkaline battery ×2, Instruction Manual×1