Detail Https://bapj.co.id/product/aemc-ac-current-probe-model-mn09/#:~:text=A
Alat Laboratorium Mikrobiologi
Deskripsi produk
AC Current Probe Model MN09
The small, compact MINI 09 current clamp is an ideal complement for any multimeter to measure AC currents in low-power tertiary or industrial applications.
Its DC voltage output enables you to overcome the low AC sensitivity of certain measuring instruments.
Main features of the MINI 09 model:
Rated current: 150 AAC
Output signal: DC voltage
Output / input ratio: 100 mVDC / AAC
Output via lead and isolated Ø 4 mm male plugs
Specifications:
Maximum Conductor Size
0.39" (10mm)
Current Range
150AAC
Measurement Range
1 to 150A
Output
5ft (1.5m) lead with 4mm safety banana plug
Transformation Ratio
N/A
Output Signal
100mVDC/AAC (150AAC / 15VDC)
Accuracy 50/60Hz
1 to 5A, 10% ±0.2A
5 to 15A 6% ±0.2A
15 to 40A 3% ±0.2A
40 to 150A ±4%
Frequency Range
48 to 65Hz
Phase Shift At 50Hz
N/A
Open Secondary Voltage
≤30V
Load Impedance
≥50KΩ
Overload
170A for 10 min ON, 30 min OFF
Dimensions (H x W x D)
4.43 x 1.48 x 1.02” (112.5 x 37.5 x 26mm)
Weight
6.5 oz (180g)
Operating Temperature
14° to +122°F (-10° to +50°C)
Storage Temperature
-40° to +176°F ( -40° to +80°C)
Operating Humidity
<85% RH
Pollution Degree
2
Ingress Protection (Ip)
IP40
EMC
EN 61326-1
Safety Compliance
EN/IEC 61010-032 600V CAT III , 300 V CAT IV Pollution Degree 2