Detail KYORITSU Multi Function Testers KEW 6516
Alat Laboratorium Mikrobiologi
Deskripsi produk
A lot of Testing Power in the hands of Electrical Installation Professionals!
DISPLAY ・Color LCD 3.5 inches dot matrix.
ATT ・Anti-Trip Technology (with 2 & 3 wire) for no trip LOOP L-PE testing on all RCDs.
・With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
LOOP ・High test current range of 2Ω with 0.001Ω resolution.
・Zs Limit compares the values required by Electrical Installations Standard with
measured results.
RCD ・Type AC, A, F, B(General & Selective), EV and Variable RCDs.
・Single and Auto test, Ramp test and Contact voltage.
EARTH ・Earth resistance test 2 and 3 wires with all accessories included.
INSULATION ・Resistance test 100, 250, 500 & 1000V with auto discharge voltage.
CONTINUITY ・Continuity test at 200mA or 15mA with selectable buzzer for fast judgment.
PHASE ROTATION ・On 3-phase lines with clear indication of the sequence on the display.
VOLTS ・TRMS Voltage measurements 2-600V, Mains Frequency.
HELP ・Display shows how to connect the instrument according to the function selected.
SPD ・Surge Protection Device test, for SPD that uses varistor.
PAT ・Portable Appliance Tester function, for Insulation and Protective conductor resistance test
SAFETY ・IEC 61010-1 CAT IV 300 V, CAT III 600 V. IEC 61557-1,2,3,4,5,6,7,10.
Various features
Large LCD & HELP function
All the test data is shown in one large colored screen.
HELP function will show how to connect the instrument according to the function selected
Operation in 3 simple steps & Hands free testing
Set the rotary dial to your testing range.
Connect the instrument to the installation under test.
Press the test button.(By remote probe or using the Lockdown function of the test button.)
Anti-Trip Technology (with 2 & 3 wire)
For no trip LOOP L-PE testing on all RCDs.
With 3 wire (L, N, PE), to get the best accuracy readings.
With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).
Loop Impedance 0.001 resolution
High test current range of 2Ω with 0.001Ω resolution.
Zs/Ra Limit
Zs Limit compares the values required by Electrical Installations Standard with measured results.
The verification of safety requirement on an electrical installation is simplified by using Zs/Ra Limit function. This function will automatically check if the measured loop impedance for TN (or earth loop for TT) is low enough to trip (disconnect) the MCB / Fuse / RCD giving the result of PASS or FAIL on the display.
SPD test
SPD (Surge Protection Device) which contains varistor can be tested measuring the tripping voltage without damage it.
PAT test
PAT test (PAT = Portable Appliance Tester) It is possible to check the insulation resistance and earth bond continuity of portable appliances for class I and II.
Connectivity
Use the PC application KEW Report to inprove work efficiency.
KEW 6516 can download the test data by connecting the USB adaptor (Model 8212-USB) and then print complete Test Reports by a PC.
Insulation resistance
SPD(Varistor)
Test
voltage
100V
250V
500V
1000V
Max.1000V
Measuring
ranges
2.000/20.00/200.0MΩ
(Auto-ranging)
20.00/200.0/1000MΩ
(Auto-ranging)
20.00/200.0/2000MΩ
(Auto-ranging)
0-1000V
(goes up by 1V)
Accuracy
±2%rdg±6dgt
(2.000/20.00MΩ)
±5%rdg±6dgt
(200.0MΩ)
±2%rdg±6dgt
(20.00/200.0MΩ)
±5%rdg±6dgt
(1000MΩ)
±2%rdg±6dgt
(20.00/200.0MΩ)
±5%rdg±6dgt
(2000MΩ)
±5%rdg±5dgt
Rated
current
1.0-1.2mA
@0.1MΩ
1.0-1.2mA
@0.25MΩ
1.0-1.2mA
@0.5MΩ
1.0-1.2mA
@1MΩ
‐
Short circuit current
1.5mA max
‐
Loop impedance
Function
LOOP ATT
LOOP HIGH
L-PE/L-N
(3wire)
L-PE
(2wire)
L-PE
(0.01ΩRes)
L-PE
(0.001ΩRes)
High test
current(25A)
L-N/L-L
Rated
voltage
100-260V
(50/60Hz)
48-260V
(50/60Hz)
48-260V
(50/60Hz)
100-260V
(50/60Hz)
48-500V
(50/60Hz)
Impedance
range
20.00/200.0/2000Ω
(Auto-ranging)
20.00/200.0/
2000Ω
(Auto-ranging)
2.000Ω
20.00Ω
Accuracy
±3%rdg±6dgt
±3%rdg±10dgt
±3%rdg±4dgt
±3%rdg±25mΩ
±3%rdg±4dgt
Nominal
test
current at
0Ω external
loop:
Magnitude/
Duration at 230V
L-N:6A/60ms
N-PE:10mA
L-PE:15mA
20Ω:
6A/20ms
200Ω:
0.5A/20ms
2000Ω:
15mA/500ms
25A/20ms
6A/20ms
PSC/PFC
Range
2000A/20kA
(L-N(PSC)/
L-PE(PFC))
2000A/20kA
(PFC)
2000A/20kA
(PFC)
2000A/50kA
(PFC)
2000A/20kA
(PSC)
Accuracy
PSC/PFC accuracy is derived from measured loop impedance specification
and measured voltage specification
RCD
Rated voltage
100-260V(50/60Hz)
Function
x1/2, x1,x5,Ramp,Auto,Uc
6/10/30/100/300/500/1000mA/variable
RCD type
AC(G/S)
A(G/S)
F(G/S)
B(G/S)
EV
Trip
current
setting
x1/2,
x1,Uc
10/30/100/300/
500/1000mA(G)
10/30/100/
300/500(S)
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300mA
6mA(x1 only)
x5
10/30/100mA
10/30/100mA
10/30/100mA
10/30mA
-
Ramp
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300mA
6mA
Accuracy
Trip
current
x1/2
-8% - -2%
-10% - 0%
-10% - 0%
-10% - 0%
-
x1
+2% - +8%
0% - +10%
0% - +10%
0% - +10%
0% - +10%
x5
+2% - +8%
0% - +10%
0% - +10%
0% - +10%
-
Ramp
-4% - +4%
-10% - +10%
-10% - +10%
-10% - +10%
-10% - +10%
Trip
time
x1/2
2000ms(G/S):±1%rdg±2ms
-
x1
550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms
10.5s:±1%±2㎳
x5
410ms(G/S):±1%rdg±2ms
-
Continuity
Range
20.00/200.0/2000Ω (Auto-ranging)
Open circuit voltage(DC)
7-14V
Measuring current
200mA
>200mA or more(2Ω or less)
15mA
15mA±3mA(short-circuit)
Accuracy
±2%rdg±8dgt
Volts
Range
300.0/600V(Auto-ranging)
Measuring ranges
Volts
2-600V
Frequency
45-65Hz
Accuracy
Volts
±2%rdg±4dgt
Frequency
±0.5%rdg±2dgt
Phase Rotation
Rated voltage
48-600V(50/60Hz)
Remarks
Remarks Correct phase sequence: are displayed “1.2.3” and mark
Reversed phase sequence: are displayed “3.2.1” and mark
Earth
Range
20.00/200.0/2000Ω(Auto-ranging)
Accuracy
±2%rdg±0.08Ω(20.00Ω)
±2%rdg±3dgt(200.0/2000Ω)
Applicable standards
IEC 61010-1 CAT IV 300V ,CAT III 600 V Pollution degree 2
IEC 61010-2-034
IEC 61557-1,2,3,4,5,6,7,10
IEC 60529(IP40)
IEC 61326(EMC)
Power source
LR6 (AA) (1.5V) ×8
Communication interface
USB
Dimensions / Weight
136(L) × 235(W) × 114(D) mm / Approx. 1350g (including batteries)
Included Accessories
Main test lead※1
7281(Test leads with remote control switch)
7246(Distribution board test lead)
7228A(Earth resistance test leads)
8041(Auxiliary earth spikes[2 spikes/1 set])
9084(Soft case)
9142(Carrying case)
9151(Shoulder strap)
9199(Shoulder pad)
8212-USB(USB adaptor with "KEW Report(Software)'')
LR6(AA) × 8, Instruction manual, Calibration certificate
Optional Accessories
8259(Adapter for measurement terminal)
7272(Precision measurement Cord set)
8017A(Extension prod long)
※1 7187A:British plug, 7218A:(EU)European SHUKO plug, 7221A:(SA)South african plug, 7222A:(AU)Australian plug
Hubungi :
Juni Tarigan (Mr.)
0811 198 0702
Pera (Ms.)
0811 3801 0819
Admin
0813-2310-201
PT. ANDALAN BANGUN SEJAHTERA
Jl. Sumur Batu No. 1, Kemayoran
Jakarta Pusat - Indonesia 10640
Telp : +6221-42803207, 4227517
Fax : +6221-42803208